CA EPBD Dynamic Database of Publications
Advanced search

Key Indicators & Decisions (KI&Ds) – EXISTING BUILDINGS

Last updated: 30 November 2022, 08:19

03.01

Is the level of nearly zero energy (NZEB) for existing buildings set in national legislation?

Comment

Austria

No

NZEB for Existing Buildings not required by Article 9 of 2010/31/EU

Belgium – Brussels Capital Region 

No
Belgium – Flemish Region Partly: only for deep renovations that are considered equivalent to new buildings

Deep renovations (in this context): large new or rebuilt building volumes > 800 m³ or containing a new residential unit.

‘Deep renovations’ as described in 2.II.i will meet the NZEB target E60 (see 03.03) for existing buildings in the near future.

Maximum U-values for all renovations are the same as the requirements for new buildings.

Belgium – Walloon Region No The next LTRS version (10 March 2020) will set an average criterion on the building park. This strategy will have to be approved by the Walloon Government in 2020
Bulgaria Yes
Croatia No
Cyprus Yes
Czech Republic No The building owner can, however, ask the EPC issuer to prepare recommendations in order to meet the NZEB requirements (even though not set as legislative requirements for renovations).
Denmark

According to (EU) 2016/1318 2.5, 'Refurbishment into NZEB' means a refurbishment of a magnitude that allows the energy performance requirements of a NZEB level to be met.

Thus, the level of NZEB is found in the Building Regulations 2018 (BR18) § 259 for residential buildings and § 260 for non-residential buildings.

Commission Recommendation (EU) 2016/1318 of 29 July 2016 on guidelines for the promotion of nearly zero-energy buildings and best practices to ensure that, by 2020, all new buildings are nearly zero-energy buildings
Estonia Yes
Finland Yes
France No It is set by seals (80 KWh/m².year)
Germany Not defined

Greece

At least energy class B+
Hungary No
Ireland Yes
Italy Yes In Decree 26.06.2015 'Minimum requirements'
Republic of Latvia Yes

(Regulations No.383, point 17., requirements for NZEB)

17. A building shall be classified as a nearly-zero energy building, if it meets all of the following requirements:

17.1. building energy performance indicator corresponds to Class A by concurrently ensuring conformity of indoor climatic conditions with the requirements of the laws and regulations in the field of construction, hygiene and labour protection;

17.2. the total primary energy consumption for heating, hot water supply, mechanical ventilation, cooling, lighting accounts for no more than 95 kWh per square meter per year;

17.3. high-efficiency systems are used in the building, which:

17.3.1 ensure recovery of no less than 75% of the ventilation heat loss during the heating season;

17.3.2. ensure at least partial use of renewable energy;

17.4. there is no fossil fuel heating equipment installed in the building.

Luxembourg Not yet, in development
Malta No. This level is set within documents forming part of regulations which are supported by legislation. The levels are set in documents which have been issued and the issue has been made public by means of a government notice.
Norway Not yet decided
Poland No
Portugal No
Slovak Republic Yes In the Act 555/2005 as amended by Act 300/2012 art. 2, section 8
Slovenia Yes
Sweden Yes
UK – England No
UK – Wales No
The Netherlands No
UK – Northern Ireland No
UK – Scotland No

03.02

Is the level of nearly zero energy (NZEB) for existing buildings similar to the level for new buildings?

Comment

Austria

No

NZEB for Existing Buildings not required by Article 9 of 2010/31/EU

Belgium – Brussels Capital Region 

Above a certain level, major renovation NZEB requirements are the 'same as for new buildings'. Other existing buildings should reach the target defined in the long-term renovation strategy.
Belgium – Flemish Region Partly: only for deep renovations that are considered equivalent to new buildings See 03.01 and 03.03
Belgium – Walloon Region Yes. For existing buildings, this will be an average requirement for the building stock that must be fulfilled by 2050. It will be the same Espec value as for new buildings. Other new buildings criteria (by example: K-level, …) will not be set for existing buildings.
Bulgaria Yes
Croatia Yes The level of NZEB in set in legislation and it refers to new buildings. In order to become NZEB, an existing building undergoing renovation shall meet the same requirements set for new buildings.
Cyprus Yes
Czech Republic Yes, partly In case of a change of an existing building, when the total energy reference area expands to at least two and a half times the original total energy reference area, NZEB requirements must be met for the whole building.
Denmark Yes, as described in 03.01
Estonia Yes, the same as for new buildings
Finland Yes
France It depends on the seals
Germany See 03.01

Greece

No, there is a differentiation (energy class A for new buildings, and energy class B+ for existing ones).
Hungary No
Ireland Yes
Italy Yes
Republic of Latvia Yes, it is the same
Luxembourg Not applicable
Malta Existing buildings need to abide by minimum energy performance requirements, but there is no requirement for abiding to NZEB level at present. The level set in minimum energy performance requirements are different from that for NZEB except for 2 building typologies.
The Netherlands No requirement
Norway Not yet decided Expectedly Yes
Poland Not specified
Portugal -
Slovak Republic Yes, they are similar to the levels of the new buildings. Existing buildings should fulfil the requirements on new buildings if technically, functionally and economically feasible
Slovenia Yes
Sweden Yes
UK – England Not defined
UK – Wales Not defined
UK – Northern Ireland Not defined
UK – Scotland Not defined

03.03

Definition of nearly zero energy (NZEB) for existing residential buildings (if different from new buildings)

Comment

Austria

N/A

NZEB for Existing Buildings not required by Article 9 of 2010/31/EU

Belgium – Brussels Capital Region 

Same as new buildings with the PECmax level requirement multiplied by 1.2
Belgium – Flemish Region

In 2050, existing residential buildings should be as efficient as a new building in 2016

Two possibilities:

  • Package of measures: maximal U-values for the components of the building envelope (roof, walls and floors Umax=0.24 W/m2.K, doors Umax=2 W/m2.K, windows 1.5 W/m2.K, and glass Umax=1.0 W/m2.K) + minimal standards for heating installations (highly energy efficient installation, cogeneration, heat pump, district heating or electrical heating of max 15 kW)
  • Energy performance score E60 of 100 kWh/m2
  1. Package of measure: additional to requirements, awareness raising in communication on proper ventilation, airtightness and solar protection
  2. Energy performance score: next to E-level, information on the performance of the envelope (S-level)
Belgium – Walloon Region Same as for new buildings
Bulgaria There is no separate definition of NZEB for existing residential buildings. The definition is the same as for the new buildings.
Croatia
Definition of NZEBs for existing buildings is the same as for new buildings.
Cyprus -
Czech Republic No
Denmark Same as new buildings
Estonia Same as new buildings
Finland na
France

Germany See 03.01

Greece

At least energy class B+
Hungary

Ireland Yes
Italy Identical to new buildings: see 02.06
Republic of Latvia It is the same as for new buildings
Luxembourg

Not applicable


Malta NZEB levels have not been defined for existing buildings.
The Netherlands

Norway Not yet decided
Poland Not specified
Portugal -
Slovak Republic Definition is the same as for new buildings. Definition: Nearly zero-energy building means a building has a very high energy performance. The nearly zero or very low amount of energy required to use such a building should be provided with effective thermal protection and covered to a very significant extent by energy from renewable sources, including energy from renewable sources produced on-site or nearby.
Slovenia

Primary energy

95 kWh/m2 (single-family)

90 kWh/m2 (multi-family)

and 50% RES


Sweden

UK – England Not defined
UK – Wales Not defined
UK – Northern Ireland Not defined
UK – Scotland Not defined

03.04

Definition of nearly zero energy (NZEB) for existing non-residential buildings (if different from new buildings)

Comment

Austria

N/A

NZEB for Existing Buildings not required by Article 9 of 2010/31/EU

Belgium – Brussels Capital Region 

Same as new buildings with the PECmax level requirement multiplied by 1.2
Belgium – Flemish Region No specific definition
Belgium – Walloon Region NZEB requirement for non-residential needs to be reshaped to use Espec instead of EW.
Bulgaria There is no separate definition of NZEB for existing non-residential buildings. The definition is the same as for the new buildings.
Croatia
Definition of NZEBs for existing buildings is the same as for new buildings.
Cyprus -
Czech Republic No
Denmark Same as new buildings
Estonia Same as new buildings
Finland na
France

Germany See 03.01

Greece

At least energy class B+
Hungary

Ireland Yes
Italy Identical to new buildings: see 02.08
Republic of Latvia -
Luxembourg

Not applicable


Malta NZEB level has not been set for existing levels When buildings undergo renovations of a range that the renovated building may be considered a new building, NZEB requirements apply.
The Netherlands Study ongoing, see 3.2 and 3.3
Norway Not yet decided
Poland Not specified
Portugal -
Slovak Republic Definition is the same as for new buildings. Is the same as for new buildings
Slovenia 65 kWh/m2 and 50% RES
Sweden No
UK – England Not defined
UK – Wales Not defined
UK – Northern Ireland Not defined
UK – Scotland Not defined

03.05

Overall minimum requirements in case of major-renovation

Comment

Austria

fGEE ≤ 1.00

See “National plan” dated February2018

fGEE = relation between final energy demand of the building and final energy demand of the corresponding reference building

Belgium – Brussels Capital Region 

For renovations with a less than 75% change in the envelope and replacement of all technical installations:

U-value requirement (Annex XIV): (Table 3)

Ventilation rate:

  • Residential (Annex XIX)
  • Non-residential (Annex XX)


Definition for units considered as new:

A greater than 75% change in the envelope and replacement of all technical installations


Requirements:

U-value requirement (Annex XIV) (Table 3)

Ventilation rate (Annexes XIX & XX)

Net Heating Requirement (for residential buildings only): 1.2 * max (15; X) kWh/m².year

Primary Energy Requirement (for residential and non-residential buildings): Same as new buildings with the PECmax level requirement multiplied by 1.2


Belgium – Flemish Region

Major renovation (as in EPBD) can be:

  • Renovation equivalent to new buildings: see above
  • Major energy renovation (75% of the envelope + replacement of the installations): E70
  • Renovation: no E-level, but requirements on renovated building parts and renovated systems

Belgium – Walloon Region The building unit should aim to reach Class A (Espec ≤ 85 kWh/m²) by 2050. An individual renovation roadmap will show the way to go for the building.
The building passport will monitor the path taken by the buildings’ stock on its way to 2050.
Bulgaria

In case of major-renovation the buildings meet the requirement for energy efficiency when the value of their integrated energy efficiency indicator ("specific annual expenditure of primary energy" in kWh/m2) corresponds, at least, to:

  • energy efficiency class “B”, for buildings commissioned after 1 February 2010 (the same requirements as those for new buildings – see item 2.1 and 2.2 above), or to
  • energy efficiency class “C”, for buildings commissioned before 1 February 2010, as given in the table below:


Croatia

Major renovation of a building means the renovation of a building where more than 25% of the surface of the envelope undergoes renovation.

In the case of major renovation, the heat transmission coefficient of the entire building element shall fulfil the prescribed requirements.

Buildings undergoing major renovation shall fulfil at least 10% of energy demand from RES which can be obtained from district or block heating based entirely or partially on energy from RES unless it is technically, functionally and economically feasible.

When reconstruction covers more than 75% of the surface of the heated building envelope, requirements are set on QH,nd, Eprim, Edel.



Cyprus B
Czech Republic Yes

Combination of energy performance indicators must be fulfilled by either:

  • primary energy and average U-value or

  • total delivered energy per year and average U-value or

  • U-value of each construction element within the system boundary and energy efficiency of the technical building systems

Denmark

BR18:

  • Energy demand in relation to conversions and replacement of building parts § 274 – 279
  • Renovation classes for existing buildings § 280 – 282

Estonia See column ‘Renovation of existing building (class C)’ in Table 2
Finland

There are different formulae to be applied for calculating the building's specific total energy consumption requirement (E-value, kWh/m2), when the design and execution of the improvements in the building's energy efficiency are based on reducing energy consumption in the building's standard use (alternative 3):

1) Single-family homes, row and chain houses, small apartment buildings: E-required ≤ 0.8 x E-calculated

2) Apartment buildings: E-required ≤ 0.85 x E-calculated

3) Office buildings: E-required ≤ 0.7 x E-calculated

4) Education buildings: E-required ≤ 0.8 x E-calculated

5) Day care centre: E-required ≤ 0.8 x E-calculated

6) Commercial buildings: E-required ≤ 0.7 x E-calculated

7) Commercial accommodation buildings: E-required ≤ 0.7 x E-calculated

8) Sports halls, does not apply to indoor ice rinks and swimming pools: E-required ≤ 0.8 x E-calculated

9) Hospitals: E-required ≤ 0.8 x E-calculated

10) Other buildings: sections 4 and 7 to be applied


France To reach a minimum energy performance standard set depending on the location of the building
Germany

Yes, 140% of the performance requirements of the reference building

Overall requirement as alternative option, only in cases of relevant major renovations

There are two options by which the requirements can be met:

  1. By meeting the requirements for renovated building elements
  2. By meeting 140% of the performance requirements for a new building (status 2014)

The requirements for the building stock consist of conditional requirements in case of relevant refurbishments, some mandatory update requirements to be met without any triggering measures, and requirements in case of extensions.

Greece

When a building undergoes major renovation, it must meet the minimum requirements of the KENAK (i.e., Class B). This is until the dates that the NZEB comes into force (1/1/2019 for public buildings, 1/1/2021 for all buildings) and then all existing buildings that undergo major renovation should be at least of Class B+.
Hungary From 2018, cost-optimal requirements must be fulfilled.

See 2.1 and 2.2.

Major renovation: if min. 25% of the building shell area is subject to energy retrofit.

Ireland Yes
Italy

According to decree 26.06.2015, the requirements in case of major renovation are structured as follows:

First-level major renovation: same requirements as new buildings (see 02.02)

Second-level major renovation:

  • U-value of the concerned surfaces lower than the limit values 

  • H'T mean transmission heat transfer coefficient of refurbished building elements lower that the limit value.

  • Mean efficiencies of renovated technical systems higher than reference values.

First- and second-level major renovations are defined as follows:

First-level major renovation: 'refurbishment of at least 50% of the envelope and renovation of the heating and/or cooling plant of the entire building'.

Second-level major renovation: 'refurbishment of at least 25% of the external surfaces of the building with or without renovation of the heating and/or cooling plant'.

For U limit values - see Table 6

For H'T limit values – see Table 4

For mean efficiencies limit values - see Table 3

Republic of Latvia
Requirements for U values are the same as for new buildings (see 2.1. and 2.2.)
Luxembourg No
Malta Buildings which have elements being replaced need to adhere to minimum energy performance requirements even if the renovation is not considered a major renovation.

E.g., all elements have a maximum U-value; glazing is limited according to orientation to limit overheating.

The Netherlands Yes

Four categories/situations can be differentiated in regard to renovation:

  1. Renovation: this shall refer to the partial renovation, renewal, or alteration, or expansion of a building. Article 5.6 Building Code, paragraph 1: The legally obtained level shall apply to thermal insulation with Rc = 1.3 m2K/W as the lower bound. The legally obtained level also applies to the airflow rate.
  2. Renovation by renewing or replacing insulation layers. Article 5.6 Building code, paragraph 2: Thermal insulation Rc at least 2.5 m2K/W for floor / 1.3 m2K/W for façade / 2,0 m2K/W for roof. Umax. = 2.2 W/m2K on average regarding windows, doors, etc., or the legally obtained level if this provides better energy performance.
  3. Major renovation and/or the total construction or entire renovation of a dormer or of a corresponding construction as referred to in Annex II of the Environmental Law Decree. Article 5.6, paragraph 3 Thermal insulation (see table 5.1 of the Building Code: Rc at least 3.5 m2K/W for floor / 4.5 m2K/W for façade)
  4. Renovation with modifications to the technical building system: a (partial) renovation, modification or expansion of the technical building system (read: the technical equipment). Article 6.55 Building code, table 6.55, system efficiencies (as of 10 March 2020)

Norway Same as for new buildings

See above. In general, when measures are applied to existing buildings the same requirements are used as for new buildings. This includes extensions, additions, underpinning, change of use, etc.

___

The local authorities can give exemptions from the requirements under certain conditions. This applies to necessary remodelling, renovation and change of use, and in cases when for example the requirements will be unreasonable compared to the energy savings the measures will provide.

Poland Not specified
Portugal Additional requirements exist when a major renovation occurs Major renovation is when >25% of the building value is spend on building elements
Slovak Republic Definition of major renovation (according to Act 555/2005 as amended by 300/2012): Bbuilding construction modifications to an existing building which affect more than 25% of its surface area, in particular by thermal insulation of the peripheral and roof structures and replacement of the openings. U-values in W/(m2.K) (e.g. external walls 0.22, roof 0.15, windows 1.0); heat recovery min. 60%; global indicator kWh/(m2.year) A1: apartment buildings less than 63, family houses less than 108.
Slovenia Same as for new buildings
Sweden Same as the level of nearly zero buildings
UK – England

Building Regulations are supported by Approved Documents, which set out an elemental approach for existing buildings, and “Domestic and Non‐domestic Building Services Compliance Guides” which include minimum energy efficiency standards for new and replacement of existing building systems.

Under certain circumstances additional energy efficiency measures (named “consequential improvements”) must be undertaken.


UK – Wales Please see England report.
UK – Northern Ireland

Building Regulations are supported by Technical Booklets*, which set out an elemental approach for existing buildings, and by “Domestic and Non‐domestic Building Services Compliance Guides”^ which include minimum energy efficiency standards for new and replacement of existing building systems.

Under certain circumstances additional energy efficiency measures (named “consequential improvements”) must be undertaken.

Domestic buildings:

(*) Technical Booklet F1, Conservation of fuel and power in dwellings, Department of Finance and Personnel, October 2012. Available at:

https://www.finance-ni.gov.uk/sites/default/files/publications/dfp/Technical-booklet-F1-Conservation%20of%20fuel%20and%20power%20in%20dwellings-October-2012.pdf

(^) Domestic Building Services Compliance Guide, 2018. Available at:

https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/697525/DBSCG_secure.pdf

Non-domestic buildings:

(*) Technical Booklet F2, Conservation of fuel and power in buildings other than dwellings, Department of Finance and Personnel, October 2012. Available at:

https://www.finance-ni.gov.uk/sites/default/files/publications/dfp/Technical-booklet-F2-Conservation-of-fuel-and-power-in-buildings-other-than-dwellings-October-2012.pdf

(^) Non-domestic Building Services Compliance Guide, 2018. Available at:

https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/453973/non_domestic_building_services_compliance_guide.pdf

UK – Scotland

Building Regulations apply to new works on existing buildings. Exceptions are detailed in the Technical Handbooks*.

Similarly to England, an elemental approach has been adopted for existing buildings.

In non‐domestic buildings, under certain circumstances, the existing services must be improved to meet the current performance recommendations in the Technical Handbook. This approach is referred to as “consequential improvements”.

(*) Domestic buildings:

Building Standards Technical Handbook 2019: domestic. Scottish Government, September 2019. Available at:

https://www.gov.scot/publications/building-standards-technical-handbook-2019-domestic/

Non-domestic buildings:

Building Standards Technical Handbook 2019: non-domestic. Scottish Government, September 2019. Available at:

https://www.gov.scot/publications/building-standards-technical-handbook-2019-non-domestic/

03.06

Minimum requirements for individual building parts in case of renovation

Comment

Austria

The renovation of individual parts has to follow a retrofit concept that has to be fixed in advance. The minimum requirement to be reached by the fully renovated building is fGEE ≤ 0.95

See OIB Guideline 6:2019, clause 4.3.2

fGEE = relation between final energy demand of the building and final energy demand of the corresponding reference building

Belgium – Brussels Capital Region 

U-value requirement (Annex XIV): (Table 3)

Ventilation rate:

  • Residential (Annex XIX)
  • Non-residential (Annex XX)
Annexes of the execution order of 2007/12/21 fixing the requirements concerning energy performance and indoor climate of buildings
Belgium – Flemish Region

Maximal U-values for all renovations correspond with the requirements for new buildings.

The requirements only apply to building parts that are renovated or insulated.

The table contains requirements for 2016.

The table is simplified.

Other maximum U-values are applied for certain types of internal walls and walls to adjacent parcels.


Belgium – Walloon Region

Same Umax values as for new buildings.

Partial ventilation flow rates in case of wall replacement and addition/replacement of windows

It is planned that every building will have an individual renovation roadmap with a Class A goal. The auditor performing the analysis must justify if Class A is not reachable and needs to stay as close as possible to Class A.

Works on individual building parts will have to be coherent with the roadmap.

Bulgaria

Minimum energy performance requirements are set for the renovated building elements that form part of the building envelope and that have a significant impact on the energy performance of the building envelope. The values of the heat transfer coefficient cannot be higher than the reference values of the heat transfer coefficient, specified in the tables below:

When an energy audit includes recommendations for improvement of the energy performance of building envelope itself or in combination with measures in technical building systems or devices consuming energy, the values of the heat transfer coefficient is allowed to be 10% over the reference values in the both tables above.

The technical building systems requirements apply to new buildings and the refurbishments and/or major renovations of existing buildings (when major renovations include all technical systems). The special requirements relate to:

  • parameters of systems for solar energy utilisation for domestic hot water;
  • seasonal efficiency of heat pumps with electrically driven compressors in heating mode (specific fan power SPFmin ≥ 3.5) and using thermal energy (specific fan power SPFmin ≥ 1.15);
  • seasonal efficiency of the air-to-air recuperators of ventilation and AC systems in heating mode ηr,min ≥ 70%;
  • efficiency of boilers (including steam boilers and boilers burning biomass at nominal and partial load) for calculating the integrated energy efficiency indicator of the building - minimum requirements are given depending on the type and capacity of the boilers and the average temperature of the heated water;
  • use of products in the buildings which must provide a high degree of environmental and health safety.

Croatia

For individual parts of buildings, a maximum allowed U-value for elements of new buildings and after reconstruction of existing buildings heated to a temperature of 18˚C or more and heated between 12˚C and 18˚C in continental and littoral climate are prescribed.

Maximum U-Value
Cyprus

0.4 W / m2 K for walls

0.4 W / m2 K for roofs and floors in contact with the external environment

2.9 W / m2 K for windows


Czech Republic Yes
Denmark Minimum requirements for individual building parts are found in BR18 Appendix 2, Table 3.
Estonia N/A
Finland

Energy efficiency requirements for each building element, see values in Table 5.

The following requirements for the technical systems of a building apply:

1) The amount of heat recovered from the exhaust air of building ventilation shall correspond to at least 45% of the amount of heat required for ventilation heating.

2) The specific electric power of a mechanical supply and exhaust air system shall not exceed 2.0 kW/(m3/s).

3) The specific electric power of a mechanical exhaust air system shall not exceed 1.0 kW/(m3/s).

4) The specific electric power of a ventilation system shall not exceed 2.5 kW/(m3/s).

5) When replacing equipment and systems, the efficiency of heating systems must be improved regarding the parts being replaced. After the replacement, the ratio between the efficiencies of the main heat production system of the building and the main heat distribution system of the premises shall be at least 0.8. The annual efficiency of the heat production system or the heat distribution system shall be at least 0.73. When the main replaced heating system of a building is a heat pump, the ratio of the Seasonal Performance Factor SPF[1] of the heat pump and the efficiency of the heat distribution system in the premises shall be at least 2.4. The specific electrical energy consumption of the accessories of a replaced heat distribution system shall be no more than 2.5 kWh/net m2 (per heated net surface area).

6) When replacing water and/or sewage systems, the regulations on new construction shall apply.


[1] Where Coefficient of Performance (COP) gives us efficiency of a heat pump at any given time, Seasonal Performance Factor (SPF) gives us the same but for annual performance of the heat pump.


France When an element of a building is being replaced, the new element must meet specific performance requirements set by law
Germany Yes, requirements on building elements and installations have to be met.

Examples for:

outer wall: Umax = 0.24 W/(m2.K)

windows: Umax = 1.3 W/(m2.K)

Minimum U-values are set depending on the element and for non-residential buildings the range of indoor temperature.

Greece

Yes, if the existing buildings undergo major renovation.
Hungary From 2018, cost-optimal requirements must be fulfilled. See 2.1.
Ireland Yes
Italy

In case of minor renovation:

  • U-value of the concerned surfaces lower than the limit values

  • Mean efficiencies of renovated technical building systems higher than reference values.

Minor renovation is defined a 'refurbishment of less than 25% of the external surfaces of the building and/or modification of the heating and/or cooling plants'.

For U limit values - see Table 6

For mean efficiencies limit values - see Table 3

Republic of Latvia

15.2 Minimum permissible level of energy performance of buildings for buildings to be reconstructed or renovated:

15.2 1. for multi-apartment residential house – energy performance indicator for heating does not exceed 90 kWh per square meter per year;

15.2 2. for one-apartment and two-apartment residential buildings of different types – energy performance indicator for heating does not exceed 100 kWh per square meter per year;

15.2 3. for non-residential buildings – energy performance indicator for heating does not exceed 110 kWh per square meter per year.

Requirements for major renovation are set in Regulation No.383 point 15.2.
Luxembourg Yes, the same minimum requirements as for new buildings
Malta

For Offices and mixed-use buildings where use includes Offices this is
350 kWh/m2 year.

All dwellings 140 kWh/m2 year

Renovations which affect a building by 25% or more of its volume before such an intervention, or where renovation of 25% or more of windows or roofs or external walls is made, or where renovation of 25% or more of any energy consuming installations for artificial lighting, or heating or cooling of air or water or space ventilation is made, or where a change-of-use permit is submitted to the Malta Environment and Planning Authority.
The Netherlands Yes See 03.05
Norway The absolute minimum requirements for new buildings will apply.

___

Max U-value: exterior wall 0.22 W/(m2K)

Max U-value: roof 0.18 W/(m2K)

Max U-value: exposed floors 0.18 W/(m2K)

Max U-value: windows/doors 1.20 W/(m2K)

Minimum airtightness (Max air changes/hour at 50 Pa pressure difference) 1.5

Poland Minimum requirements for renovated buildings are fulfilled when walls and technical building systems comply with the requirements for thermal insulation specified in Annex 2 of the regulation, and the window thermal characteristics comply with the requirements specified in §2.1 of Annex 2 (section 2.I. -Tables 1 - 5).
Portugal

Yes, minimum requirements for renovated building parts exist, and must comply with following levels:


Slovak Republic Duty to fulfil the requirements on U-value (after national standard STN 73 0540-2:2012, STN 73 0540-2/Z1:2016) since 1 August 2016 has been set for ultra-low energy buildings (Ur1); STN 73 0540-2+Z1+Z2:2019 since 1 July 2019 has been set for NZEB (Ur2); in the case where it is functionally, technically and economically not feasible implementing the proposed measure, the building part subject to renovation must satisfy the requirement to fulfil certain hygienic criteria (in such a case the U-value should be lower than Umax (Table 1).

The Slovak Republic is characterised by one climatic zone.

External wall Umax: 0.46; Ur1: 0.22

Roof               Umax: 0.30; Ur1: 0.15

Windows        Umax: 1.70; Ur1: 1.00

Slovenia

Same as for new buildings

Uwall = 0.28 W/m2K, Uroof = 0.20 W/m2K, Uwindows = 1.30 W/m2K


Sweden

Tabell 9:92 Ui [W/m2K]

Ui [W/m2K]

Utak 0.13 (roof)

Uvägg 0.18 (outer wall)

Ugolv 0.15 (floor)

Ufönster 1.2 (window)

Uytterdörr 1.2 (door)

(BFS 2011:26).

Tabell 9:95 Maximum values for SFP (specific fan power for one ventilation system) respectively

SFPv (Specific fan power for one unit)

SFP, [kW/(m3/s)] SFPv [kW/(m3/s)]

Exhaust and supply air ventilation with heat recovery 2.0

Exhaust and supply air ventilation without heat recovery 1.5

Exhaust air ventilation with heat recovery 1.0

Exhaust air ventilation 0.6

(BFS 2011:26).


UK – England Ditto 03.05
UK – Wales Ditto 03.05
UK – Northern Ireland Ditto 03.05
UK – Scotland Ditto 03.05

03.07

National targets for renovation in connection to Long Term Renovation Strategy (number or percentage of buildings)

Comment

Austria

N/A


Belgium – Brussels Capital Region 

All residential units will have to meet a PECmax requirement of 100 kWh/(m².y) on average.
Belgium – Flemish Region

Evolution to a yearly 3% renovation rate of residential buildings towards label A

(95,000 dwellings/year)

If renovations are staged (e.g. starting with an evolution from label F to label C, and in a next phase to label A) then the actual percentage of buildings that need works each year will be higher (up to 10%).
Belgium – Walloon Region The residential building stock must be 'Class A' (Espec ≤ 85 kWh/m²) on average; impact expected on all buildings.
Bulgaria

Croatia



Cyprus 1%
Czech Republic Yes See the table in section 2.II.iv.
Denmark Work on the national targets is currently underway.
Estonia 3% of public buildings
Finland na Baseline for calculation is the existing building stock of 2020. Targets are not related to the number or percentage of buildings. The existing building stock of 2020 (100%) is estimated to be only 70% by 2050.
France

Germany

Greece



Hungary

Ireland Yes
Italy

Target 2030:

  • 0.8% for residential sector

  • 4% for tertiary sector

Target 2050:

  • 1.2% for residential sector

  • 3.7% for tertiary sector

Annual deep renovation rate to achieve the savings objectives to 2030 and 2050 - NECP
(these targets are currently being discussed within the framework of the approval of the STREPIN)
Republic of Latvia

Luxembourg 1.6% per year in 2030 for residential buildings
Malta Renovation rate to reach 3.3% per annum during period 2025-2030
The Netherlands

The built environment accounts for more than 30% of total energy consumption in the Netherlands. In order to achieve the long-term goals for energy and climate, it is therefore essential to make the national building stock more sustainable in the run-up to 2050. In line with the broader energy and climate policy of the Netherlands, the government will focus primarily on CO2 reduction in making the built environment more sustainable. This means that CO2 emission ceilings have been chosen and that progress will be measured in Mton CO2.

For the built environment, this is 3.4 Mton of additional CO2 reduction in 2030 compared to existing and planned policy. According to this indicative allocation, the maximum CO2 emissions for the built environment in 2030 will be 15.3 Mton.

The Netherlands has no indicative allocation of CO2 targets to sectors by 2050. That is why the indicative milestone was used for the built environment for 2050 as a direct translation of the general 95% CO2 reduction target. A CO2 reduction of 95% in the built environment in 2050 compared to 1990 is equivalent to a maximum emission of 1.5 Mton CO2 equivalents. This is the indicative milestone that the Netherlands will use for 2050.

To determine the indicative milestone for the built environment for 2040, a linear decrease in greenhouse gas emissions is assumed between the indicative milestones for 2030 and 2050. The indicative milestone then amounts to a maximum emission of 8.4 Mton CO2 equivalents.

The Netherlands emphasises that these are indicative objectives. In a next version of the National Energy and Climate Plan (NECP), these objectives can be adjusted downwards or upwards if developments (for example around the cost-effectiveness of the energy transition or innovation) give cause to do so.

Norway Not applicable
Poland According to the recommended scenario, by 2050 66% of buildings will be brought to a passive standard (up to 50 kWh/(m2.year)), and 21% to an energy-saving standard (50-90 kWh/(m2.year). The remaining 13% of buildings, which for technical or economic reasons cannot be thoroughly modernised , will be in the efficiency range of 90-150 kWh/(m2.year).
Portugal

The Portuguese Long Term Renovation Strategy has four (4) different renovation packages which apply according to the building need/performance:

  • Package 1 - Improving the comfort and mitigating Energy Poverty through improvements in the building’s envelope:

- Up to 2030: 65% of existing dwellings (applies to the worst performing residential buildings built prior to 1990);

- Up to 2040: 100% of existing dwellings;

  • Package 2.1 – Improving Energy Efficiency (lighting and equipment):

- Up to 2030: 65% of existing dwellings (applies to the worst performing residential buildings built prior to 1990) and 27% of non-residential buildings;
- Up to 2040: 100% of existing dwellings and 52% of non-residential buildings;
- Up to 2050: 100% of the existing building stock;

  • Package 2.2 – Improving Energy Efficiency (HVAC systems):

- Up to 2030: 23% of existing dwellings (applies to the worst performing residential buildings built prior to 1990 which needs active systems to guarantee thermal comfort) and 27% of non-residential buildings;
- Up to 2040: 77% of existing dwellings and 52% of non-residential buildings;
- Up to 2050: 100% of the existing building stock;

  • Package 3 – Local Decarbonisation (through RES such as solar thermal, PVs and heat pumps):

- Up to 2030: 23% of existing dwellings (applies to residential buildings that improved their systems) and 27% of non-residential buildings;
- Up to 2040: 75% of existing dwellings and 52% of non-residential buildings;
- Up to 2050: 100% of the existing building stock;

  • Package 4 – Thermal Comfort improvement (through an increase of the availability and use of HVAC systems):

- Up to 2030: not expected to change significantly;
- Up to 2040: 65% of existing dwellings and 52% of non-residential buildings;
- Up to 2050: 100% of the existing building stock.

  • Globally (meaning the implementation of at least one renovation package), these targets are as follows:

- Up to 2030: 69% of the existing building stock;
- Up to 2040: 99% of the existing building stock;
- Up to 2050: 100% of the existing building stock (all packages in all existing building stock).

The reference year for the existing stock to which the percentages refers is 2020.
Slovak Republic National targets are currently subject to approval by the government.
Slovenia By 2050, 74% of single-family houses and 91% of multi-family houses shall be energy renovated.
Sweden

Expected percentage of renovated buildings (apartment buildings, schools, offices) in 2020:

  • 15-25% for buildings built up to 1980
  • About 2% for buildings built after 1980

UK – England Not defined
UK – Wales Please see England report.
UK – Northern Ireland Refer to the England report for details.
UK – Scotland Not defined

03.08

National targets for renovation in connection to Long Term Renovation Strategy (expected reductions and relevant years)

Comment

Austria

N/A


Belgium – Brussels Capital Region 

The target has to be reached by 2050 but the renovation will be planned from 2025 until 2050 in order to achieve this goal. In compliance with the EPC, renovation works must happen for each dwelling/unit every five (5) years from 2025 until the target is met.
Belgium – Flemish Region

Final energy use residential:

  • 2030: - 23%
  • 2040: - 46%
  • 2050: - 69%

Belgium – Walloon Region Reduction of the energy consumption (EPB-related uses of energy) of residential buildings by 62% compared to 2005.
Bulgaria

Croatia



Cyprus Around 33,000 residential buildings and 10,000 non-residential buildings are expected to be renovated by 2030.
Czech Republic Yes See the table in section 2.II.iv.
Denmark

Expected reduction of net heat energy consumption for residential buildings:

 

2017

2020

2025

2030

kWh/m2

119,7

118,7

116,0

113,4


Estonia Buildings built before 2000 (totalling 54 million m2) – percentage to be renovated to class C: 22% by 2030, 64% by 2040, 100% by 2050. For class C, see Table 2
Finland

Residential and non-residential buildings total, heating energy consumption (gross) compared to 2020: 100% (2020), 78% (2030), 64% (2040) and 51% (2050).

Residential and non-residential buildings total, heating energy consumption (delivered energy) compared to 2020: 100% (2020), 70% (2030) 51% (2040), and 38% (2050).

Residential and non-residential buildings total, CO2 emissions compared to 2020: 100% (2020), 37% (2030), 19% (2040), and 8% (2050).

According to the roadmap laid out in the Finnish LTRS, the reduction of energy consumption (gross) is 55%, compared to the heating energy consumption of buildings in 2005.

The heating energy consumption (gross) will be reduced by 50 % by 2050 compared to 2020.

The expected consumption of delivered heating energy will be reduced approximately by 60 % by 2050 compared to 2020.

The CO2 emissions from the heating energy consumption of the building stock will be reduced by 92% in the period 2020-2050.

France

Germany Emissions of the Building Sector reduced to 70 Mio. t CO2 until 2030

Greece



Hungary

111 PJ reduction by 2030 for the whole building stock18

yearly 3% deep renovation of central govermental buildings15

Ireland Yes
Italy

0.33 Mtoe / year of final energy for residential sector

0.24 Mtoe / year of final energy for the tertiary sector

Reduction Targets - NECP Scenario 2020-2030

Republic of Latvia



Luxembourg 1,827 GWh (final energy consumption (FEC) in 2020 - FEC in 2030) for residential buildings
Malta Reduction of 74% in energy use in the residential sector and reduction of 78% of energy demand in the non-residential sector
The Netherlands
See 03.07
Norway Not applicable
Poland

Generally, the final energy saving potential is expected to total over 155,000 GWh. As a result, it will be possible to reduce over 46 million tonnes of CO2 and almost 90 thousand tons of dust.

The estimated cumulative number of renovations will amount to 2.34 million by 2030, 4.98 million by 2040, and 7.21 million by 2050.


Portugal

Primary Energy Reduction:

  • Up to 2030: 11%
  • Up to 2040: 27%
  • Up to 2050: 34%

CO2 Emissions Reduction:

  • Up to 2030: 15%
  • Up to 2040: 47%
  • Up to 2050: 77%

Hours of Thermal Discomfort Reduction:

  • Up to 2030: 26%
  • Up to 2040: 34%
  • Up to 2050: 56%
The reference year to which the percentages refer is 2020.
Slovak Republic National targets for expected reductions and milestones are currently subject to approval by the government.
Slovenia A final energy reduction of 45% and a CO2 reduction of 75% compared to the base year 2005, are planned until 2050. Greenhouse gas emissions shall be reduced by 75% (base year: 2005), and the share of RES shall be increased to at least two thirds of the energy use (without electricity and district heat) until 2030.
Sweden

Expected energy efficiency 2020-2050 according to the reference scenario (purchased heat):

  • Apartment buildings: -17.7%
  • Schools: -13.6%
  • Offices: - 3.4%<

UK – England Not defined
UK – Wales Please see England report.
UK – Northern Ireland Refer to the England report for details.
UK – Scotland Not defined

Copyright © 2024 CA EPBD