Key Indicators & Decisions (KI&Ds) – EXISTING BUILDINGS
03.01 |
Is the level of nearly zero energy (NZEB) for existing buildings set in national legislation? |
Comment |
---|---|---|
Austria |
No |
NZEB for Existing Buildings not required by Article 9 of 2010/31/EU |
Belgium – Brussels Capital Region |
No | |
Belgium – Flemish Region | Partly: only for deep renovations that are considered equivalent to new buildings | Deep renovations (in this context): large new or rebuilt building volumes > 800 m³ or containing a new residential unit. ‘Deep renovations’ as described in 2.II.i will meet the NZEB target E60 (see 03.03) for existing buildings in the near future. Maximum U-values for all renovations are the same as the requirements for new buildings. |
Belgium – Walloon Region | No | The next LTRS version (10 March 2020) will set an average criterion on the building park. This strategy will have to be approved by the Walloon Government in 2020 |
Bulgaria | Yes | |
Croatia | No | |
Cyprus | Yes | |
Czech Republic | No | The building owner can, however, ask the EPC issuer to prepare recommendations in order to meet the NZEB requirements (even though not set as legislative requirements for renovations). |
Denmark | According to (EU) 2016/1318 2.5, 'Refurbishment into NZEB' means a refurbishment of a magnitude that allows the energy performance requirements of a NZEB level to be met. Thus, the level of NZEB is found in the Building Regulations 2018 (BR18) § 259 for residential buildings and § 260 for non-residential buildings. |
Commission Recommendation (EU) 2016/1318 of 29 July 2016 on guidelines for the promotion of nearly zero-energy buildings and best practices to ensure that, by 2020, all new buildings are nearly zero-energy buildings |
Estonia | Yes | |
Finland | Yes | |
France | No | It is set by seals (80 KWh/m².year) |
Germany | Not defined | |
Greece |
At least energy class B+ | |
Hungary | No | |
Ireland | Yes | |
Italy | Yes | In Decree 26.06.2015 'Minimum requirements' |
Republic of Latvia | Yes | (Regulations No.383, point 17., requirements for NZEB) 17. A building shall be classified as a nearly-zero energy building, if it meets all of the following requirements: 17.1. building energy performance indicator corresponds to Class A by concurrently ensuring conformity of indoor climatic conditions with the requirements of the laws and regulations in the field of construction, hygiene and labour protection; 17.2. the total primary energy consumption for heating, hot water supply, mechanical ventilation, cooling, lighting accounts for no more than 95 kWh per square meter per year; 17.3. high-efficiency systems are used in the building, which: 17.3.1 ensure recovery of no less than 75% of the ventilation heat loss during the heating season; 17.3.2. ensure at least partial use of renewable energy; 17.4. there is no fossil fuel heating equipment installed in the building. |
Luxembourg | Not yet, in development | |
Malta | No. This level is set within documents forming part of regulations which are supported by legislation. | The levels are set in documents which have been issued and the issue has been made public by means of a government notice. |
Norway | Not yet decided | |
Poland | No | |
Portugal | No | |
Slovak Republic | Yes | In the Act 555/2005 as amended by Act 300/2012 art. 2, section 8 |
Slovenia | Yes | |
Sweden | Yes | |
UK – England | No | |
UK – Wales | No | |
The Netherlands | No | |
UK – Northern Ireland | No | |
UK – Scotland | No |
03.02 |
Is the level of nearly zero energy (NZEB) for existing buildings similar to the level for new buildings? |
Comment |
---|---|---|
Austria |
No |
NZEB for Existing Buildings not required by Article 9 of 2010/31/EU |
Belgium – Brussels Capital Region |
Above a certain level, major renovation NZEB requirements are the 'same as for new buildings'. Other existing buildings should reach the target defined in the long-term renovation strategy. | |
Belgium – Flemish Region | Partly: only for deep renovations that are considered equivalent to new buildings | See 03.01 and 03.03 |
Belgium – Walloon Region | Yes. For existing buildings, this will be an average requirement for the building stock that must be fulfilled by 2050. It will be the same Espec value as for new buildings. | Other new buildings criteria (by example: K-level, …) will not be set for existing buildings. |
Bulgaria | Yes | |
Croatia | Yes | The level of NZEB in set in legislation and it refers to new buildings. In order to become NZEB, an existing building undergoing renovation shall meet the same requirements set for new buildings. |
Cyprus | Yes | |
Czech Republic | Yes, partly | In case of a change of an existing building, when the total energy reference area expands to at least two and a half times the original total energy reference area, NZEB requirements must be met for the whole building. |
Denmark | Yes, as described in 03.01 | |
Estonia | Yes, the same as for new buildings | |
Finland | Yes | |
France | It depends on the seals | |
Germany | See 03.01 | |
Greece |
No, there is a differentiation (energy class A for new buildings, and energy class B+ for existing ones). | |
Hungary | No | |
Ireland | Yes | |
Italy | Yes | |
Republic of Latvia | Yes, it is the same | |
Luxembourg | Not applicable | |
Malta | Existing buildings need to abide by minimum energy performance requirements, but there is no requirement for abiding to NZEB level at present. | The level set in minimum energy performance requirements are different from that for NZEB except for 2 building typologies. |
The Netherlands | No requirement | |
Norway | Not yet decided | Expectedly Yes |
Poland | Not specified | |
Portugal | - | |
Slovak Republic | Yes, they are similar to the levels of the new buildings. | Existing buildings should fulfil the requirements on new buildings if technically, functionally and economically feasible |
Slovenia | Yes | |
Sweden | Yes | |
UK – England | Not defined | |
UK – Wales | Not defined | |
UK – Northern Ireland | Not defined | |
UK – Scotland | Not defined |
03.03 |
Definition of nearly zero energy (NZEB) for existing residential buildings (if different from new buildings) |
Comment |
---|---|---|
Austria |
N/A |
NZEB for Existing Buildings not required by Article 9 of 2010/31/EU |
Belgium – Brussels Capital Region |
Same as new buildings with the PECmax level requirement multiplied by 1.2 | |
Belgium – Flemish Region | In 2050, existing residential buildings should be as efficient as a new building in 2016 Two possibilities:
|
|
Belgium – Walloon Region | Same as for new buildings | |
Bulgaria | There is no separate definition of NZEB for existing residential buildings. The definition is the same as for the new buildings. | |
Croatia | Definition of NZEBs for existing buildings is the same as for new buildings. | |
Cyprus | - | |
Czech Republic | No | |
Denmark | Same as new buildings | |
Estonia | Same as new buildings | |
Finland | na | |
France | ||
Germany | See 03.01 | |
Greece |
At least energy class B+ | |
Hungary | ||
Ireland | Yes | |
Italy | Identical to new buildings: see 02.06 | |
Republic of Latvia | It is the same as for new buildings | |
Luxembourg | Not applicable |
|
Malta | NZEB levels have not been defined for existing buildings. | |
The Netherlands | ||
Norway | Not yet decided | |
Poland | Not specified | |
Portugal | - | |
Slovak Republic | Definition is the same as for new buildings. | Definition: Nearly zero-energy building means a building has a very high energy performance. The nearly zero or very low amount of energy required to use such a building should be provided with effective thermal protection and covered to a very significant extent by energy from renewable sources, including energy from renewable sources produced on-site or nearby. |
Slovenia | Primary energy 95 kWh/m2 (single-family) 90 kWh/m2 (multi-family) and 50% RES |
|
Sweden | ||
UK – England | Not defined | |
UK – Wales | Not defined | |
UK – Northern Ireland | Not defined | |
UK – Scotland | Not defined |
03.04 |
Definition of nearly zero energy (NZEB) for existing non-residential buildings (if different from new buildings) |
Comment |
---|---|---|
Austria |
N/A |
NZEB for Existing Buildings not required by Article 9 of 2010/31/EU |
Belgium – Brussels Capital Region |
Same as new buildings with the PECmax level requirement multiplied by 1.2 | |
Belgium – Flemish Region | No specific definition | |
Belgium – Walloon Region | NZEB requirement for non-residential needs to be reshaped to use Espec instead of EW. | |
Bulgaria | There is no separate definition of NZEB for existing non-residential buildings. The definition is the same as for the new buildings. | |
Croatia | Definition of NZEBs for existing buildings is the same as for new buildings. | |
Cyprus | - | |
Czech Republic | No | |
Denmark | Same as new buildings | |
Estonia | Same as new buildings | |
Finland | na | |
France | ||
Germany | See 03.01 | |
Greece |
At least energy class B+ | |
Hungary | ||
Ireland | Yes | |
Italy | Identical to new buildings: see 02.08 | |
Republic of Latvia | - | |
Luxembourg | Not applicable |
|
Malta | NZEB level has not been set for existing levels | When buildings undergo renovations of a range that the renovated building may be considered a new building, NZEB requirements apply. |
The Netherlands | Study ongoing, see 3.2 and 3.3 | |
Norway | Not yet decided | |
Poland | Not specified | |
Portugal | - | |
Slovak Republic | Definition is the same as for new buildings. | Is the same as for new buildings |
Slovenia | 65 kWh/m2 and 50% RES | |
Sweden | No | |
UK – England | Not defined | |
UK – Wales | Not defined | |
UK – Northern Ireland | Not defined | |
UK – Scotland | Not defined |
03.05 |
Overall minimum requirements in case of major-renovation |
Comment |
---|---|---|
Austria |
fGEE ≤ 1.00 |
See “National plan” dated February2018 fGEE = relation between final energy demand of the building and final energy demand of the corresponding reference building |
Belgium – Brussels Capital Region |
For renovations with a less than 75% change in the envelope and replacement of all technical installations: U-value requirement (Annex XIV): (Table 3) Ventilation rate:
Definition for units considered as new: A greater than 75% change in the envelope and replacement of all technical installations Requirements: U-value requirement (Annex XIV) (Table 3) Ventilation rate (Annexes XIX & XX) Net Heating Requirement (for residential buildings only): 1.2 * max (15; X) kWh/m².year Primary Energy Requirement (for residential and non-residential buildings): Same as new buildings with the PECmax level requirement multiplied by 1.2 |
|
Belgium – Flemish Region | Major renovation (as in EPBD) can be:
|
|
Belgium – Walloon Region | The building unit should aim to reach Class A (Espec ≤ 85 kWh/m²) by 2050. | An individual renovation roadmap will show the way to go for the building. The building passport will monitor the path taken by the buildings’ stock on its way to 2050. |
Bulgaria |
In case of major-renovation the buildings meet the requirement for energy efficiency when the value of their integrated energy efficiency indicator ("specific annual expenditure of primary energy" in kWh/m2) corresponds, at least, to:
|
|
Croatia |
Major renovation of a building means the renovation of a building where more than 25% of the surface of the envelope undergoes renovation. In the case of major renovation, the heat transmission coefficient of the entire building element shall fulfil the prescribed requirements. Buildings undergoing major renovation shall fulfil at least 10% of energy demand from RES which can be obtained from district or block heating based entirely or partially on energy from RES unless it is technically, functionally and economically feasible. When reconstruction covers more than 75% of the surface of the heated building envelope, requirements are set on QH,nd, Eprim, Edel.
|
|
Cyprus | B | |
Czech Republic | Yes | Combination of energy performance indicators must be fulfilled by either:
|
Denmark | BR18:
|
|
Estonia | See column ‘Renovation of existing building (class C)’ in Table 2 | |
Finland | There are different formulae to be applied for calculating the building's specific total energy consumption requirement (E-value, kWh/m2), when the design and execution of the improvements in the building's energy efficiency are based on reducing energy consumption in the building's standard use (alternative 3): 1) Single-family homes, row and chain houses, small apartment buildings: E-required ≤ 0.8 x E-calculated 2) Apartment buildings: E-required ≤ 0.85 x E-calculated 3) Office buildings: E-required ≤ 0.7 x E-calculated 4) Education buildings: E-required ≤ 0.8 x E-calculated 5) Day care centre: E-required ≤ 0.8 x E-calculated 6) Commercial buildings: E-required ≤ 0.7 x E-calculated 7) Commercial accommodation buildings: E-required ≤ 0.7 x E-calculated 8) Sports halls, does not apply to indoor ice rinks and swimming pools: E-required ≤ 0.8 x E-calculated 9) Hospitals: E-required ≤ 0.8 x E-calculated 10) Other buildings: sections 4 and 7 to be applied |
|
France | To reach a minimum energy performance standard set depending on the location of the building | |
Germany | Yes, 140% of the performance requirements of the reference building Overall requirement as alternative option, only in cases of relevant major renovations |
There are two options by which the requirements can be met:
The requirements for the building stock consist of conditional requirements in case of relevant refurbishments, some mandatory update requirements to be met without any triggering measures, and requirements in case of extensions. |
Greece |
When a building undergoes major renovation, it must meet the minimum requirements of the KENAK (i.e., Class B). This is until the dates that the NZEB comes into force (1/1/2019 for public buildings, 1/1/2021 for all buildings) and then all existing buildings that undergo major renovation should be at least of Class B+. | |
Hungary | From 2018, cost-optimal requirements must be fulfilled. | See 2.1 and 2.2. Major renovation: if min. 25% of the building shell area is subject to energy retrofit. |
Ireland | Yes | |
Italy | According to decree 26.06.2015, the requirements in case of major renovation are structured as follows: First-level major renovation: same requirements as new buildings (see 02.02) Second-level major renovation:
|
First- and second-level major renovations are defined as follows: First-level major renovation: 'refurbishment of at least 50% of the envelope and renovation of the heating and/or cooling plant of the entire building'. Second-level major renovation: 'refurbishment of at least 25% of the external surfaces of the building with or without renovation of the heating and/or cooling plant'. For U limit values - see Table 6 For H'T limit values – see Table 4 For mean efficiencies limit values - see Table 3 |
Republic of Latvia | Requirements for U values are the same as for new buildings (see 2.1. and 2.2.) | |
Luxembourg | No | |
Malta | Buildings which have elements being replaced need to adhere to minimum energy performance requirements even if the renovation is not considered a major renovation. | E.g., all elements have a maximum U-value; glazing is limited according to orientation to limit overheating. |
The Netherlands | Yes | Four categories/situations can be differentiated in regard to renovation:
|
Norway | Same as for new buildings | See above. In general, when measures are applied to existing buildings the same requirements are used as for new buildings. This includes extensions, additions, underpinning, change of use, etc. ___ The local authorities can give exemptions from the requirements under certain conditions. This applies to necessary remodelling, renovation and change of use, and in cases when for example the requirements will be unreasonable compared to the energy savings the measures will provide. |
Poland | Not specified | |
Portugal | Additional requirements exist when a major renovation occurs | Major renovation is when >25% of the building value is spend on building elements |
Slovak Republic | Definition of major renovation (according to Act 555/2005 as amended by 300/2012): Bbuilding construction modifications to an existing building which affect more than 25% of its surface area, in particular by thermal insulation of the peripheral and roof structures and replacement of the openings. | U-values in W/(m2.K) (e.g. external walls 0.22, roof 0.15, windows 1.0); heat recovery min. 60%; global indicator kWh/(m2.year) A1: apartment buildings less than 63, family houses less than 108. |
Slovenia | Same as for new buildings | |
Sweden | Same as the level of nearly zero buildings | |
UK – England | Building Regulations are supported by Approved Documents, which set out an elemental approach for existing buildings, and “Domestic and Non‐domestic Building Services Compliance Guides” which include minimum energy efficiency standards for new and replacement of existing building systems. Under certain circumstances additional energy efficiency measures (named “consequential improvements”) must be undertaken. |
|
UK – Wales | Please see England report. | |
UK – Northern Ireland | Building Regulations are supported by Technical Booklets*, which set out an elemental approach for existing buildings, and by “Domestic and Non‐domestic Building Services Compliance Guides”^ which include minimum energy efficiency standards for new and replacement of existing building systems. Under certain circumstances additional energy efficiency measures (named “consequential improvements”) must be undertaken. |
Domestic buildings: (*) Technical Booklet F1, Conservation of fuel and power in dwellings, Department of Finance and Personnel, October 2012. Available at: (^) Domestic Building Services Compliance Guide, 2018. Available at: Non-domestic buildings: (*) Technical Booklet F2, Conservation of fuel and power in buildings other than dwellings, Department of Finance and Personnel, October 2012. Available at: (^) Non-domestic Building Services Compliance Guide, 2018. Available at: |
UK – Scotland | Building Regulations apply to new works on existing buildings. Exceptions are detailed in the Technical Handbooks*. Similarly to England, an elemental approach has been adopted for existing buildings. In non‐domestic buildings, under certain circumstances, the existing services must be improved to meet the current performance recommendations in the Technical Handbook. This approach is referred to as “consequential improvements”. |
(*) Domestic buildings: Building Standards Technical Handbook 2019: domestic. Scottish Government, September 2019. Available at: https://www.gov.scot/publications/building-standards-technical-handbook-2019-domestic/ Non-domestic buildings: Building Standards Technical Handbook 2019: non-domestic. Scottish Government, September 2019. Available at: https://www.gov.scot/publications/building-standards-technical-handbook-2019-non-domestic/ |
03.06 |
Minimum requirements for individual building parts in case of renovation |
Comment |
---|---|---|
Austria |
The renovation of individual parts has to follow a retrofit concept that has to be fixed in advance. The minimum requirement to be reached by the fully renovated building is fGEE ≤ 0.95 |
See OIB Guideline 6:2019, clause 4.3.2 fGEE = relation between final energy demand of the building and final energy demand of the corresponding reference building |
Belgium – Brussels Capital Region |
U-value requirement (Annex XIV): (Table 3) Ventilation rate:
|
Annexes of the execution order of 2007/12/21 fixing the requirements concerning energy performance and indoor climate of buildings |
Belgium – Flemish Region |
Maximal U-values for all renovations correspond with the requirements for new buildings.
The requirements only apply to building parts that are renovated or insulated. The table contains requirements for 2016. The table is simplified. Other maximum U-values are applied for certain types of internal walls and walls to adjacent parcels. |
|
Belgium – Walloon Region | Same Umax values as for new buildings. Partial ventilation flow rates in case of wall replacement and addition/replacement of windows |
It is planned that every building will have an individual renovation roadmap with a Class A goal. The auditor performing the analysis must justify if Class A is not reachable and needs to stay as close as possible to Class A. Works on individual building parts will have to be coherent with the roadmap. |
Bulgaria |
Minimum energy performance requirements are set for the renovated building elements that form part of the building envelope and that have a significant impact on the energy performance of the building envelope. The values of the heat transfer coefficient cannot be higher than the reference values of the heat transfer coefficient, specified in the tables below:
When an energy audit includes recommendations for improvement of the energy performance of building envelope itself or in combination with measures in technical building systems or devices consuming energy, the values of the heat transfer coefficient is allowed to be 10% over the reference values in the both tables above. The technical building systems requirements apply to new buildings and the refurbishments and/or major renovations of existing buildings (when major renovations include all technical systems). The special requirements relate to:
|
|
Croatia |
For individual parts of buildings, a maximum allowed U-value for elements of new buildings and after reconstruction of existing buildings heated to a temperature of 18˚C or more and heated between 12˚C and 18˚C in continental and littoral climate are prescribed.
|
Maximum U-Value |
Cyprus | 0.4 W / m2 K for walls 0.4 W / m2 K for roofs and floors in contact with the external environment 2.9 W / m2 K for windows |
|
Czech Republic | Yes | |
Denmark | Minimum requirements for individual building parts are found in BR18 Appendix 2, Table 3. | |
Estonia | N/A | |
Finland | Energy efficiency requirements for each building element, see values in Table 5. The following requirements for the technical systems of a building apply: 1) The amount of heat recovered from the exhaust air of building ventilation shall correspond to at least 45% of the amount of heat required for ventilation heating. 2) The specific electric power of a mechanical supply and exhaust air system shall not exceed 2.0 kW/(m3/s). 3) The specific electric power of a mechanical exhaust air system shall not exceed 1.0 kW/(m3/s). 4) The specific electric power of a ventilation system shall not exceed 2.5 kW/(m3/s). 5) When replacing equipment and systems, the efficiency of heating systems must be improved regarding the parts being replaced. After the replacement, the ratio between the efficiencies of the main heat production system of the building and the main heat distribution system of the premises shall be at least 0.8. The annual efficiency of the heat production system or the heat distribution system shall be at least 0.73. When the main replaced heating system of a building is a heat pump, the ratio of the Seasonal Performance Factor SPF[1] of the heat pump and the efficiency of the heat distribution system in the premises shall be at least 2.4. The specific electrical energy consumption of the accessories of a replaced heat distribution system shall be no more than 2.5 kWh/net m2 (per heated net surface area). 6) When replacing water and/or sewage systems, the regulations on new construction shall apply. [1] Where Coefficient of Performance (COP) gives us efficiency of a heat pump at any given time, Seasonal Performance Factor (SPF) gives us the same but for annual performance of the heat pump. |
|
France | When an element of a building is being replaced, the new element must meet specific performance requirements set by law | |
Germany | Yes, requirements on building elements and installations have to be met. | Examples for: outer wall: Umax = 0.24 W/(m2.K) windows: Umax = 1.3 W/(m2.K) Minimum U-values are set depending on the element and for non-residential buildings the range of indoor temperature. |
Greece |
Yes, if the existing buildings undergo major renovation. | |
Hungary | From 2018, cost-optimal requirements must be fulfilled. | See 2.1. |
Ireland | Yes | |
Italy | In case of minor renovation:
|
Minor renovation is defined a 'refurbishment of less than 25% of the external surfaces of the building and/or modification of the heating and/or cooling plants'. For U limit values - see Table 6 For mean efficiencies limit values - see Table 3 |
Republic of Latvia | 15.2 Minimum permissible level of energy performance of buildings for buildings to be reconstructed or renovated: 15.2 1. for multi-apartment residential house – energy performance indicator for heating does not exceed 90 kWh per square meter per year; 15.2 2. for one-apartment and two-apartment residential buildings of different types – energy performance indicator for heating does not exceed 100 kWh per square meter per year; 15.2 3. for non-residential buildings – energy performance indicator for heating does not exceed 110 kWh per square meter per year. |
Requirements for major renovation are set in Regulation No.383 point 15.2. |
Luxembourg | Yes, the same minimum requirements as for new buildings | |
Malta | For Offices and mixed-use buildings where use includes Offices this is All dwellings 140 kWh/m2 year |
Renovations which affect a building by 25% or more of its volume before such an intervention, or where renovation of 25% or more of windows or roofs or external walls is made, or where renovation of 25% or more of any energy consuming installations for artificial lighting, or heating or cooling of air or water or space ventilation is made, or where a change-of-use permit is submitted to the Malta Environment and Planning Authority. |
The Netherlands | Yes | See 03.05 |
Norway | The absolute minimum requirements for new buildings will apply. | ___ Max U-value: exterior wall 0.22 W/(m2K) Max U-value: roof 0.18 W/(m2K) Max U-value: exposed floors 0.18 W/(m2K) Max U-value: windows/doors 1.20 W/(m2K) Minimum airtightness (Max air changes/hour at 50 Pa pressure difference) 1.5 |
Poland | Minimum requirements for renovated buildings are fulfilled when walls and technical building systems comply with the requirements for thermal insulation specified in Annex 2 of the regulation, and the window thermal characteristics comply with the requirements specified in §2.1 of Annex 2 (section 2.I. -Tables 1 - 5). | |
Portugal |
Yes, minimum requirements for renovated building parts exist, and must comply with following levels:
|
|
Slovak Republic | Duty to fulfil the requirements on U-value (after national standard STN 73 0540-2:2012, STN 73 0540-2/Z1:2016) since 1 August 2016 has been set for ultra-low energy buildings (Ur1); STN 73 0540-2+Z1+Z2:2019 since 1 July 2019 has been set for NZEB (Ur2); in the case where it is functionally, technically and economically not feasible implementing the proposed measure, the building part subject to renovation must satisfy the requirement to fulfil certain hygienic criteria (in such a case the U-value should be lower than Umax (Table 1). | The Slovak Republic is characterised by one climatic zone. External wall Umax: 0.46; Ur1: 0.22 Roof Umax: 0.30; Ur1: 0.15 Windows Umax: 1.70; Ur1: 1.00 |
Slovenia | Same as for new buildings Uwall = 0.28 W/m2K, Uroof = 0.20 W/m2K, Uwindows = 1.30 W/m2K |
|
Sweden | Tabell 9:92 Ui [W/m2K] Ui [W/m2K] Utak 0.13 (roof) Uvägg 0.18 (outer wall) Ugolv 0.15 (floor) Ufönster 1.2 (window) Uytterdörr 1.2 (door) (BFS 2011:26). Tabell 9:95 Maximum values for SFP (specific fan power for one ventilation system) respectively SFPv (Specific fan power for one unit) SFP, [kW/(m3/s)] SFPv [kW/(m3/s)] Exhaust and supply air ventilation with heat recovery 2.0 Exhaust and supply air ventilation without heat recovery 1.5 Exhaust air ventilation with heat recovery 1.0 Exhaust air ventilation 0.6 (BFS 2011:26). |
|
UK – England | Ditto 03.05 | |
UK – Wales | Ditto 03.05 | |
UK – Northern Ireland | Ditto 03.05 | |
UK – Scotland | Ditto 03.05 |
03.07 |
National targets for renovation in connection to Long Term Renovation Strategy (number or percentage of buildings) |
Comment |
---|---|---|
Austria |
N/A |
|
Belgium – Brussels Capital Region |
All residential units will have to meet a PECmax requirement of 100 kWh/(m².y) on average. | |
Belgium – Flemish Region | Evolution to a yearly 3% renovation rate of residential buildings towards label A (95,000 dwellings/year) |
If renovations are staged (e.g. starting with an evolution from label F to label C, and in a next phase to label A) then the actual percentage of buildings that need works each year will be higher (up to 10%). |
Belgium – Walloon Region | The residential building stock must be 'Class A' (Espec ≤ 85 kWh/m²) on average; impact expected on all buildings. | |
Bulgaria | ||
Croatia |
|
|
Cyprus | 1% | |
Czech Republic | Yes | See the table in section 2.II.iv. |
Denmark | Work on the national targets is currently underway. | |
Estonia | 3% of public buildings | |
Finland | na | Baseline for calculation is the existing building stock of 2020. Targets are not related to the number or percentage of buildings. The existing building stock of 2020 (100%) is estimated to be only 70% by 2050. |
France | ||
Germany | ||
Greece |
||
Hungary | ||
Ireland | Yes | |
Italy | Target 2030:
Target 2050:
|
Annual deep renovation rate to achieve the savings objectives to 2030 and 2050 - NECP (these targets are currently being discussed within the framework of the approval of the STREPIN) |
Republic of Latvia | ||
Luxembourg | 1.6% per year in 2030 for residential buildings | |
Malta | Renovation rate to reach 3.3% per annum during period 2025-2030 | |
The Netherlands | The built environment accounts for more than 30% of total energy consumption in the Netherlands. In order to achieve the long-term goals for energy and climate, it is therefore essential to make the national building stock more sustainable in the run-up to 2050. In line with the broader energy and climate policy of the Netherlands, the government will focus primarily on CO2 reduction in making the built environment more sustainable. This means that CO2 emission ceilings have been chosen and that progress will be measured in Mton CO2. For the built environment, this is 3.4 Mton of additional CO2 reduction in 2030 compared to existing and planned policy. According to this indicative allocation, the maximum CO2 emissions for the built environment in 2030 will be 15.3 Mton. The Netherlands has no indicative allocation of CO2 targets to sectors by 2050. That is why the indicative milestone was used for the built environment for 2050 as a direct translation of the general 95% CO2 reduction target. A CO2 reduction of 95% in the built environment in 2050 compared to 1990 is equivalent to a maximum emission of 1.5 Mton CO2 equivalents. This is the indicative milestone that the Netherlands will use for 2050. To determine the indicative milestone for the built environment for 2040, a linear decrease in greenhouse gas emissions is assumed between the indicative milestones for 2030 and 2050. The indicative milestone then amounts to a maximum emission of 8.4 Mton CO2 equivalents. The Netherlands emphasises that these are indicative objectives. In a next version of the National Energy and Climate Plan (NECP), these objectives can be adjusted downwards or upwards if developments (for example around the cost-effectiveness of the energy transition or innovation) give cause to do so. |
|
Norway | Not applicable | |
Poland | According to the recommended scenario, by 2050 66% of buildings will be brought to a passive standard (up to 50 kWh/(m2.year)), and 21% to an energy-saving standard (50-90 kWh/(m2.year). The remaining 13% of buildings, which for technical or economic reasons cannot be thoroughly modernised , will be in the efficiency range of 90-150 kWh/(m2.year). | |
Portugal | The Portuguese Long Term Renovation Strategy has four (4) different renovation packages which apply according to the building need/performance:
- Up to 2030: 65% of existing dwellings (applies to the worst performing residential buildings built prior to 1990); - Up to 2040: 100% of existing dwellings;
- Up to 2030: 65% of existing dwellings (applies to the worst performing residential buildings built prior to 1990) and 27% of non-residential buildings;
- Up to 2030: 23% of existing dwellings (applies to the worst performing residential buildings built prior to 1990 which needs active systems to guarantee thermal comfort) and 27% of non-residential buildings;
- Up to 2030: 23% of existing dwellings (applies to residential buildings that improved their systems) and 27% of non-residential buildings;
- Up to 2030: not expected to change significantly;
- Up to 2030: 69% of the existing building stock; |
The reference year for the existing stock to which the percentages refers is 2020. |
Slovak Republic | National targets are currently subject to approval by the government. | |
Slovenia | By 2050, 74% of single-family houses and 91% of multi-family houses shall be energy renovated. | |
Sweden | Expected percentage of renovated buildings (apartment buildings, schools, offices) in 2020:
|
|
UK – England | Not defined | |
UK – Wales | Please see England report. | |
UK – Northern Ireland | Refer to the England report for details. | |
UK – Scotland | Not defined |
03.08 |
National targets for renovation in connection to Long Term Renovation Strategy (expected reductions and relevant years) |
Comment |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Austria |
N/A |
|||||||||||
Belgium – Brussels Capital Region |
The target has to be reached by 2050 but the renovation will be planned from 2025 until 2050 in order to achieve this goal. In compliance with the EPC, renovation works must happen for each dwelling/unit every five (5) years from 2025 until the target is met. | |||||||||||
Belgium – Flemish Region | Final energy use residential:
|
|||||||||||
Belgium – Walloon Region | Reduction of the energy consumption (EPB-related uses of energy) of residential buildings by 62% compared to 2005. | |||||||||||
Bulgaria | ||||||||||||
Croatia |
|
|||||||||||
Cyprus | Around 33,000 residential buildings and 10,000 non-residential buildings are expected to be renovated by 2030. | |||||||||||
Czech Republic | Yes | See the table in section 2.II.iv. | ||||||||||
Denmark | Expected reduction of net heat energy consumption for residential buildings:
|
|||||||||||
Estonia | Buildings built before 2000 (totalling 54 million m2) – percentage to be renovated to class C: 22% by 2030, 64% by 2040, 100% by 2050. | For class C, see Table 2 | ||||||||||
Finland | Residential and non-residential buildings total, heating energy consumption (gross) compared to 2020: 100% (2020), 78% (2030), 64% (2040) and 51% (2050). Residential and non-residential buildings total, heating energy consumption (delivered energy) compared to 2020: 100% (2020), 70% (2030) 51% (2040), and 38% (2050). Residential and non-residential buildings total, CO2 emissions compared to 2020: 100% (2020), 37% (2030), 19% (2040), and 8% (2050). |
According to the roadmap laid out in the Finnish LTRS, the reduction of energy consumption (gross) is 55%, compared to the heating energy consumption of buildings in 2005. The heating energy consumption (gross) will be reduced by 50 % by 2050 compared to 2020. The expected consumption of delivered heating energy will be reduced approximately by 60 % by 2050 compared to 2020. The CO2 emissions from the heating energy consumption of the building stock will be reduced by 92% in the period 2020-2050. |
||||||||||
France | ||||||||||||
Germany | Emissions of the Building Sector reduced to 70 Mio. t CO2 until 2030 | |||||||||||
Greece |
||||||||||||
Hungary | 111 PJ reduction by 2030 for the whole building stock18 yearly 3% deep renovation of central govermental buildings15 |
|||||||||||
Ireland | Yes | |||||||||||
Italy | 0.33 Mtoe / year of final energy for residential sector 0.24 Mtoe / year of final energy for the tertiary sector |
Reduction Targets - NECP Scenario 2020-2030 | ||||||||||
Republic of Latvia |
||||||||||||
Luxembourg | 1,827 GWh (final energy consumption (FEC) in 2020 - FEC in 2030) for residential buildings | |||||||||||
Malta | Reduction of 74% in energy use in the residential sector and reduction of 78% of energy demand in the non-residential sector | |||||||||||
The Netherlands | See 03.07 | |||||||||||
Norway | Not applicable | |||||||||||
Poland | Generally, the final energy saving potential is expected to total over 155,000 GWh. As a result, it will be possible to reduce over 46 million tonnes of CO2 and almost 90 thousand tons of dust. The estimated cumulative number of renovations will amount to 2.34 million by 2030, 4.98 million by 2040, and 7.21 million by 2050. |
|||||||||||
Portugal | Primary Energy Reduction:
CO2 Emissions Reduction:
Hours of Thermal Discomfort Reduction:
|
The reference year to which the percentages refer is 2020. | ||||||||||
Slovak Republic | National targets for expected reductions and milestones are currently subject to approval by the government. | |||||||||||
Slovenia | A final energy reduction of 45% and a CO2 reduction of 75% compared to the base year 2005, are planned until 2050. Greenhouse gas emissions shall be reduced by 75% (base year: 2005), and the share of RES shall be increased to at least two thirds of the energy use (without electricity and district heat) until 2030. | |||||||||||
Sweden | Expected energy efficiency 2020-2050 according to the reference scenario (purchased heat):
|
|||||||||||
UK – England | Not defined | |||||||||||
UK – Wales | Please see England report. | |||||||||||
UK – Northern Ireland | Refer to the England report for details. | |||||||||||
UK – Scotland | Not defined |