Key Indicators & Decisions (KI&Ds) – Sweden – 2021
Key Implementation Decisions – GENERAL BACKGROUND
no |
Key Implementation Decisions – General Background |
Description / value / response |
Comments |
---|---|---|---|
01.01 |
Definition of public buildings (according to article 9 b) |
NZEB-regulation applies to all buildings independent of use or ownership. A definition of public buildings is therefore not necessary. |
Fastighetstaxeringslag (1979:1152) |
01.02 |
Definition of public buildings used by the public (according to article 13) |
Lag (2006:985) om energideklaration för byggnader. |
|
01.03 |
Number of residential buildings |
Approx. 2,400,000. |
Estimated total |
01.04 |
Number of non-residential buildings |
Approx. 110,000 |
Estimated total |
01.05 |
If possible, share of public buildings included in the number given in 01.04 |
||
01.06 |
If possible, share of commercial buildings included in the number given in 01.04 |
||
01.07 |
Number of buildings constructed per year (estimate) |
Approx. 5,000 buildings |
Rough estimate relevant for 2016 |
01.08 |
If possible, share of residential buildings constructed per year (estimate, included in the number given in 01.07) |
63,000 dwellings approx. 4,000 buildings Single-family houses approx. 7,000 dwellings/year Residential apartment buildings approx. 27,000 dwellings/year |
|
01.09 |
If possible, share of non-residential buildings constructed per year (estimate, included in the number given in 01.07) |
||
01.10 |
Useful floor area of buildings constructed per year in million square meters (estimate) |
8.8 million m2 on average. |
Key Implementation Decision – NEW BUILDINGS
no |
Key Implementation Decision – New Buildings |
Description / value / response |
Comments |
---|---|---|---|
02.01 |
Are building codes set as an overall value, primary energy, environment (CO2), reference building or other? |
Overall value primary energy number |
|
02.02 |
Requirements for energy performance of residential buildings in current building code |
Building regulation (BFS 2011:6) |
|
02.03 |
Requirements for energy performance of non-residential commercial buildings in current building code |
See above; same regulation applies |
|
02.04 |
Requirements for energy performance of non-residential public buildings in current building code |
See above; same regulation applies |
|
02.05 |
Is the performance level of nearly zero energy (NZEB) for new buildings defined in national legislation? |
Yes |
|
02.06 |
Nearly zero energy (NZEB) level for residential buildings (level for building code) |
NZEB-level is set for all new buildings. |
|
02.07 |
Year/date for nearly zero energy (NZEB) as level for residential buildings (as indicated in 02.04) |
2017 |
|
02.08 |
Nearly zero energy (NZEB) level for all non-residential buildings (level for building code) |
NZEB-level is set for all new buildings. |
|
02.09 |
Year/date for nearly zero energy (NZEB) as level for non-residential buildings (as indicated in 02.06) |
2017 |
|
02.10 |
Are nearly zero energy buildings (NZEB) defined using a carbon or environment indicator? |
Environment indicator |
|
02.11 |
Is renewable energy a part of the overall or an additional requirement? |
Taken into account |
|
02.12 |
If renewable energy is an additional requirement to NZEB, please indicate level |
||
02.13 |
Specific comfort criteria for new buildings, provide specific parameters for instance for airtightness, minimum ventilation rates |
Building regulation (BFS 2011:6) |
Sec. 6 BBR |
Key Implementation Decision – EXISTING BUILDINGS
no |
Key Implementation Decision – Existing Buildings |
Description / value / response |
Comment |
---|---|---|---|
03.01 |
Is the level of nearly zero energy (NZEB) for existing buildings set in national legislation? |
Yes |
|
03.02 |
Is the level of nearly zero energy (NZEB) for existing buildings similar to the level for new buildings? |
Yes |
|
03.03 |
Definition of nearly zero energy (NZEB) for existing residential buildings (if different from new buildings) |
||
03.04 |
Definition of nearly zero energy (NZEB) for existing non-residential buildings (if different from new buildings) |
No |
|
03.05 |
Overall minimum requirements in case of major-renovation |
Same as the level of nearly zero buildings |
|
03.06 |
Minimum requirements for individual building parts in case of renovation |
Tabell 9:92 Ui [W/m2K] Ui [W/m2K] Utak 0.13 (roof) Uvägg 0.18 (outer wall) Ugolv 0.15 (floor) Ufönster 1.2 (window) Uytterdörr 1.2 (door) (BFS 2011:26). Tabell 9:95 Maximum values for SFP (specific fan power for one ventilation system) respectively SFPv (Specific fan power for one unit) SFP, [kW/(m3/s)] SFPv [kW/(m3/s)] Exhaust and supply air ventilation with heat recovery 2.0 Exhaust and supply air ventilation without heat recovery 1.5 Exhaust air ventilation with heat recovery 1.0 Exhaust air ventilation 0.6 (BFS 2011:26). |
|
03.07 |
National targets for renovation in connection to Long Term Renovation Strategy (number or percentage of buildings) |
Expected percentage of renovated buildings (apartment buildings, schools, offices) in 2020:
|
|
03.08 |
National targets for renovation in connection to Long Term Renovation Strategy (expected reductions and relevant years) |
Expected energy efficiency 2020-2050 according to the reference scenario (purchased heat):
|
Key Implementation Decision – ENERGY PERFORMANCE CERTIFICATES
no |
Key Implementation Decision – Energy Performance Certificates |
Description / value / response |
Comment |
---|---|---|---|
04.01 |
Number of energy performance certificates per year (for instance average or values for 3-5 years) |
85,000 EPCs average |
|
04.02 |
Number of EPCs since start of scheme |
680,000 (valid) + 280,000 (invalid, not yet renewed) |
|
04.03 |
Number of EPCs for different building types |
680,000 |
|
04.04 |
Number of assessors |
870 |
|
04.05 |
Basic education requirements for assessors |
Engineers CEX regulation |
|
04.06 |
Additional training demands for assessors |
Five (5) years of practical experience |
|
04.07 |
Quality assurance system |
Automatic controls Input data is controlled by software in diverse (automated) ways, for example, by climate correction and validation of administrative information on the building through other national databases. There are also programmed warnings and error messages when input data is out of a certain range. Furthermore, the calculation of energy performance is controlled by software as well. Independent energy expert Validity checks are performed automatically on every EPC when the expert is issuing the EPC. The energy expert is responsible for ensuring that the EPC is prepared correctly. Certification and accreditation bodies A certification body tests and approves the person who wants to become a certified energy expert to ensure that the energy expert meets the requirements regulated in CEX. Validity audit Boverket is required to conduct a yearly validity audit covering both input data and EPC results. |
|
04.08 |
National database for EPCs |
Yes |
|
04.09 |
Link to national information on EPCs / Database |
Publicly available: https://www.boverket.se/sv/energideklaration/sok-energideklaration/ |
Key Implementation Decision – SMART BUILDINGS AND BUILDING SYSTEMS
no |
Key Implementation Decision – Smart Buildings and Building Systems |
Description / value / response |
Comment |
---|---|---|---|
05.01 |
Is there a national definition of smart buildings? |
No |
|
05.02 |
Are there current support systems for smart buildings? |
No |
|
05.03 |
Are there currently specific requirements for technical building systems (for instance in building codes)? |
No, general requirements |
|
05.04 |
Are there current requirements for automatics (for instance in building codes)? |
No |
|
05.05 |
Chosen option A or B for heating systems (inspection or other measures) |
A |
|
05.06 |
Number of heating inspections; reports per year (if option A) |
Not yet available |
|
05.07 |
Chosen option A or B for cooling systems (inspection or other measures) |
A |
|
05.08 |
Number of AC / cooling system inspections; reports per year (if option A) |
Not yet available |
|
05.09 |
Is there a national database for heating inspections? |
Yes, as a part of the EPC database |
|
05.10 |
Is there a national database for cooling / AC inspections? |
Yes, as a part of the EPC database |
|
05.11 |
Are inspection databases combined with EPC databases for registration of EPCs and inspection reports? |
Yes, included |
|
05.12 |
Link to national information on Inspection / Database |